Gambar PRO63110-GL 10KVA
Prolink Giant I Series 3 phase UPS system uses true online double conversion technology with galvanic isolation transformer design which guarantees
to supply consistent and quality electrical power to protect your mission critical applications. DSP control technology is implemented for the system to
have improved performance and high reliability. All internal PCBAs are coated to withstand harsh environment.
Users can easily monitor and access to their UPS status from a comprehensive LCD display. The UPS systems have USB and RS-232 communication
ports as standard, with a built-in intelligent slot for additional adapters, protocol converters and relay contact cards. SNMP option is also available for
power management via SNMP manager and web browser. Giant I (3P/1P) series is available in models ranging from 10kVA to 40kVA and Giant [3P/3P]
series is from 10kVA to 200kVA. In addition, the system comes with a parallel redundant configuration option that allows four units to operate in parallel.
Key Features
• Online double-conversion
• DSP technology guarantees high reliability
• True galvanic isolation transformer design
• Control designed to withstand all kinds of loads
• Intelligent battery management to prolong battery lifecycle
• Redundant fan design and independent ventilation enhance durable operation under harsh environment
• Adjustable battery numbers
• Accept dual-mains input
• Parallel operation with up to 4 units (option)
• Varieties of communication options available
• Optional 7″ touch LCD
• Reverse phase frequency operation and supports non-neutral input
• Output Isolation Transformer

SPECIFICATIONS PRO63110-GL 10KVA

GENERAL
– UPS Type : Tower
– Phase : 3 phase in / 1 phase out
– Rating (VA) : 10KVA
– Nominal Power (W) : 8KW
– Dimension (mm) : 656 x 405 x 817 (D x W x H)
– Weight (kg) : 118
INPUT
– Connection Type : Terminal
– Nominal Voltage : 3 x 380VAC/400VAC/415VAC (3Ph or 3Ph + N)
– Acceptable Voltage Range : 285VAC ~ 475VAC
– Frequency : 50/60Hz ± 10%
INVERTER
– Connection Type : Terminal
– Nominal Voltage : 220VAC/230VAC/240VAC (Selectable)
– Frequency : 50 Hz / 60 Hz
– Frequency Synchronization Speed : 1~2 Hz/s
– Crest Factor : 3:1
– Harmonic Distortion : <2% (Linear Load) <5% (Non-linear Load)
BYPASS
-Connection Type : Hardwire 3-wire (1Ph+N+G)
– Input Voltage Range : 220VAC ± 25%
– Overload Capability : 1.5 In~1.8 In 1h~30s
– Short-circuit Capability : 1.8 In ~ >2.0 In 30s~200ms
BATTERY
– Rectifier Type : 6 pulse
– Rated output voltage : 384 VDC
– Charger voltage : 190VDC ~ 435VDC (Adjustable)
– Charging Current (max) : Default 10A. Maximum=Capacity/Battery Voltage
– Battery Type : Support VRLA Battery
– Numbers : 32 pcs ( 29 ~ 32 adjustable)
– Cold Start : Yes
REAR PANEL
1.Interface
2.Input/ Output / Bypass/ Battery Terminals
3.Breakers and switch
4.Cooling Fan
5.Communication ports / slot / terminals
6.Cold start button. This button is located same position for whole series.