Gambar PRO608-S/L 7.5KVA

Prolink Giant Series (1P/1P) Tower

true online double conversion UPS systems are using Galvanic Isolation design to withstand all kinds of loads. The UPS applies an advanced digital controller to control the double conversion system, and with an isolated transformer at the output to protect the load and the UPS itself. The system has unique ventilation design for effective heat dissipation. All internal PCBAs are coated to withstand harsh environment. The unit is able to accept wide input voltage and frequency range to withstand robust environment. Users can easily monitor and access to their UPS status from a comprehensive LCD display. The UPS systems have USB and RS-232 communication ports as standard, with a built-in intelligent slot for additional adapters, protocol converters and relay contact cards. SNMP option is also available for power management via SNMP manager and web browser. Giant (1P/1P) series are available in models ranging from 6kVA to 10kVA.

Key Features
• Galvanic isolation design to withstand all kinds of loads
• Output power factor 0.8
• Fully coating PCBAs to withstand harsh environment
• Unique ventilation design for effective heat dissipation
• Wide input voltage and frequency range to withstand robust environment
• High short-circuit and overload capabilities
• Maintenance bypass switch (option)

SPECIFICATIONS PRO608-S/L 7.5KVA

GENERAL
– UPS Type : Tower
– Phase : Single phase with ground
– Rating (VA) : 7500VA
– Nominal Power (W) : 6000W
– Standard Model Dimension (mm) : 562 x 300 x 830 (D x W x H)
– Weight (kg) : 122
– Long-run Model Dimension (mm) : 562 x 250 x 830 (D x W x H)
– Weight (kg) : 78

INPUT
– Connection Type : Terminal
– Nominal Voltage : 208VAC/220VAC/230 VAC
– Voltage Range : 165VAC ~ 275VAC @ 16 pcs of batteries 185VAC ~ 275VAC @ 18 pcs of batteries
– Frequency Range : 40 Hz ~ 55 Hz @ 50Hz system 56 Hz ~ 64 Hz @ 60Hz system

OUTPUT
– Connection Type : Terminal
– Output Voltage : 208VAC/220VAC/230 VAC
– Voltage Regulation : ±1%
– Frequency Range (Synchronized Range) : 45Hz ~ 55 Hz or 56 Hz ~ 64 Hz
– Frequency Range (Batt. Mode) : 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
– Current Crest Ratio : 3:1
– Harmonic Distortion : ≦3% THD (Linear load) ≦5% THD (Non-linear load)

ALARM & INDICATORS
– Battery Mode : Sounding every 4 seconds
– Low Battery : Sounding every second
– Overload : Sounding twice every second
– Fault : Continuously sounding
– LCD : Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators

CONNECTIVITY, CONTROL & MONITORING
– Front panel : Status LED, Function keys, LCD display
– Communication : Smart RS232* USB Port Emergency Power Off (EPO)

BATTERY
– Standard Model Type : 12V / 9Ah
– Numbers : 16
– Typical Recharge Time : 6 hours recover to 90% capacity
– Long-run Model Type : Depending on the capacity of external batteries
– Numbers : 16 / 18
– Charging Current (max) : Default :8 A ± 10%; Max: 2A, 4A, 8A (Adjustable)

Rear Panel 6-10KVA
1. Intelligent slot
2. External battery connector
3. RS-232 communication port
4. Dry contact port
5. USB communication port
6. Emergency power o function
connector (EPO connector)
7. Maintenance bypass switch (option)
8. Output Breaker
9. Bypass Breaker
10. Input circuit breaker
11. Output/Bypass/Input terminal
12. Cooling fa